Snap-Tite Hose

PONN CONQUEST (FC) HOSE

  • Sale
  • Regular price $0.00


POLYESTER DOUBLE JACKET ATTACK/SUPPLY HOSE

Today’s fires are hotter—so more water is needed at the nozzle to knock them down fast. Conquest rises to the challenge with a patented thru-the-weave extruded polyurethane liner with a smooth surface that delivers maximum water flow. Conquest logs friction loss reductions of more than 50% compared to other hose designs, delivering more water at standard operating pressure.

  • Built Better. Unique double jacket municipal fire hose made from 100% high tensile strength ring-spun polyester outer jacket covering extruded thru-the-weave polyurethane inner hose. No adhesive is used: The lining will never delaminate—100% guaranteed for the life of the hose.
  • Unmatched Durability. Exclusive Dura-Cote™ treatment increases abrasion resistance to more than 50-times that of uncoated hose, increases burn resistance by 500%, virtually eliminates water pick-up, is resistant to petrochemicals and extends the life of the hose.
  • Flexible. Remains flexible to temperatures as low as -40°F (-40°C) and meets all NFPA requirements for ozone resistance. Passes 18″ doorway kink test at 75 psi (1¾” diameter Conquest).
  • Identifiable. Optional color-coded stripe of one contrasting color can be woven into the outer jacket running the full length of the hose.
  • Versatile. Suitable for CAFS and foam concentrates. When specified for potable water, the polyurethane lining material meets NSF/ANSI Standard 61 for drinking water.
  • Certified. Manufactured in accordance with National Fire Protection Association (NFPA) 1961 Standard, latest edition within our ISO-9001 certified quality assurance system.

HOSE SIZING AND SPECIFICATION

5″300 (2070)600 (4140)900 (6200)62 (28.1)8.10″5 3/8

Size Service Test Proof Test Burst Weight
(For 50′ Coupled)
Flat Width Bowl Size Certification Available
IN PSI (kPa) PSI (kPa) PSI (kPa) LBS (KG) IN IN
1 3/4 400 (2760) 800 (5515) 1200 (8275) 19 (8.8) 3.20″ 2 3/16 UL, ULC
2″ 400 (2760) 800 (5515) 1200 (8275) 21 (9.8) 3.40″ 2 5/16
2 1/2 400 (2760) 800 (5515) 1200 (8275) 30 (13.8) 4.30″ 2 7/8 UL, ULC
3″ 300 (2070) 600 (4140) 900 (6200) 35 (15.9) 5.40″ 3 9/16
4″ 300 (2070) 600 (4140) 900 (6200) 50 (22.7) 6.90″ 4 17/32
6″ 300 (2070) 600 (4140) 900 (6200) 86 (39.0) 9.8″ 6 3/4

As per NFPA 1961 – The service test pressure is to be 10% greater than the “normal highest operating pressure” at which the hose is expected to be used.